community_w – is a password that corresponds to an SNMP community for write. It is indicate indicated at the page «SETUP» of a device web interface. It is possible to use Latin letters, numbers, character «_» without quotes and spaces.

...

Command CodeDescription
Pn+Switch on a relay n, where n is a relay number
Pn-Switch off a relay n, where n is a relay number
PnR

Reload a relay n, where n is a relay number

Warning

A polarity (direction) of switching a relay when resetting must correspond to a specified one in the settings of the module «Watchdog» (reset mode). If a relay is already is has a reset status, a reset command will not have any effect, however, a response notification about a successful execution «NP DONE PnR» will be sent to a destination number.

PnWSwitch a relay n into the management mode «Watchdog», where n - is a relay number
PnSSwitch a relay n into the management mode «Schedule», where n - is a relay number
PnXSwitch a relay n into the management mode «Schedule+Watchdog», where n - is a relay number (in the process of development)
PnLSwitch a relay n into the management mode «Logic», where n - is a relay number
Pn?Request a status of a relay n, where n - is a relay number
P?Request a status of all relays in a brief form
N?Request a status of a pinger
Tb?Request readings of a temperature sensor b, where b - is a number of a temperature sensor
Hx?Request readings of a humidity sensor x, where x - is a number of a humidity sensor
A?Request a status of a battery

...

kkkkk –is a request identifier (a random number). It is repeated in a response for setting a correspondence between a request and a response. It is an optional element of a command. If there is no identifier in a command, there is no identifier in a response

 

An incorrect passsword password (Community) in an outgoing command:

...

b  is a number of a temperature sensor

t – is a current reading of a temperature value, in °C

t1, t2 – are thresholds of a «normal range» of a temperature, in °C

kkkkk – is a request identifier (a random number). It is repeated in a response for setting a correspondence between a request and a response. It is an optional element of a command. If there is no identifier in a command, there is no identifier in a response

...

Info
iconfalse

NP REPLY Hx=h% BELOW SAFE RANGE (h1..h2%) T= tC kkkkk

NP REPLY Hx=h% IN SAFE RANGE (h1..h2%) T= tC kkkkk

NP REPLY Hx=h% ABOVE SAFE RANGE (h1..h2%) T= tC kkkkk

where:

– is a current reading value of a relative humidity, in %

h1, h2 – are thresholds of a «normal range» of a relative humidity, in %

t – is a current readings of a temperature value, in °C

kkkkk – is a request identifier (a random number). It is repeated in a response for setting a correspondence between a request and a response. It is an optional element of a command. If there is no identifier in a command, there is no identifier in a response

...

– is a power supply source, and can have the values: «220V» (220V grid power), «BATTERY» (battery power)

С – is a battery status, and can have the values: «OK» (battery is full), «LOW» (battery is low)

...