A formal description of SNMP TRAP notifications can be found in the MIB files DKSF_70.6.x_ MB.mib, DKSF_71.6.x_ MB.mib applied to the firmware of the devices UniPing server solution v3/SMS and UniPing server solution v3. They can be downloaded from the pages of the site with a description of devices in the section «Documentation and Files». SNMP TRAP notification is sent in the format SNMP v1/v2c, while the description in the MIB files has a format SNMP v2c.

...

OID

Data Type

Description

.1.3.6.1.4.1.25728.8900.2.1.0

Integer

A number of an IO line (starting from «1»), changing of which caused the sending of a TRAP notification.

.1.3.6.1.4.1.25728.8900.2.2.0

Integer

A value of a logic level at an IO line («0» or «1»).

.1.3.6.1.4.1.25728.8900.2.6.0

Octet String

Memo (a textual description of a line, encoding win1251).

.1.3.6.1.4.1.25728.8900.2.7.0Octet StringDescription of a logic level. A clear for understanding description of a numeric value of a logic level of an IO line

SNMP TRAP when Changing a Status of a Temperature Sensor

...

OID

Description

.1.3.6.1.4.1.25728.8400.6.100.n

There are no readings of a relative humidity, where n is a channel of a sensor

.1.3.6.1.4.1.25728.8400.6.101.n

Readings of a relative humidity are below normal humidity range, where n is a channel of a sensor

.1.3.6.1.4.1.25728.8400.6.102.n

Readings of a relative humidity are normal, where n is a channel of a sensor

.1.3.6.1.4.1.25728.8400.6.103.n

Readings of a relative humidity are above a normal humidity range, where n is a channel of a sensor

.1.3.6.1.4.1.25728.8400.6.127.nA common snmpTrapOID for all events, where n is a channel of a sensor
.1.3.6.1.4.1.25728.8400.6.m.99A common snmpTrapOID for all channels, where m is an event code (100, 101, 102, 103)
.1.3.6.1.4.1.25728.8400.6.127.99A common snmpTrapOID for all events and all channels


npRelHumTrapTemp iIdentification 

...

OID

Data Type

Description

.1.3.6.1.4.1.25728.8200.2.1.0

Integer

A number of a 1-wire smoke sensor (1..4), changing a status of which caused sending a TRAP notification.

.1.3.6.1.4.1.25728.8200.2.2.0

Integer

A status of a 1-wire smoke sensor

0 – Normal

1 – Alert

4 – Absent

5 – Failure

.1.3.6.1.4.1.25728.8300.2.6.0

Octet String

Memo ( the textual description of an installation place of a 1-wire smoke sensor, encoding win1251).

...