Information in the section applies to the device UniPing server solution v3/SMS with a built-in GSM modem. |
SMS notifications look like the following:
np_name (q) information |
where:
np_name – is a name of a device for identification of SMS notifications. It is specified on the page «SETUP» of a device web interface. If a name of a device is not specified, then the name «NETPING» is used
q – is a consequent number of notifications. A number is non-volatile – it is not zeroed when the power is switched off. It is used for a registration of missed (lost) notifications
Information – is an informational part of SMS notifications
Notification about changing a status of an IO line:
IOn=0|1 label transcript |
where:
n – is a number of an IO line, 1..8
label – is a label of an IO line, is specified in the field «Memo» on the page «DISCRETE IO» of a device web interface. If a label is not set (empty), then it is not included into SMS.
transcript – is a description of a logic level of an IO line, it is set in the pop-up dialogue for configuring notifications from IO lines on the page «DISCRETE IO» of a device web interface. If a description is not set (empty), then it is not included into SMS.
A notification about a failure of a temperature sensor (a sensor stopped responding while polling):
TEMP.SENSOR n "label" IS FAILED |
where:
n – is a number of a temperature sensor, 1..8
label – is a label of a temperature sensor, it is specified in the field «Memo» on the page «TEMPERATURE» of a device web interface. A label in the text of a notification is quoted. It a label is not set (empty), then it is not included into SMS
A notification about a normalization of temperature within the thresholds of a specified range on the page «TEMPERATURE» of a device web interface:
TEMP.SENSOR n "label" IN SAFE RANGE (t1 TO t2), NOW tC |
where:
n – is a number of a temperature sensor, 1..8
t1, t2 – are the thresholds of the normal temperature range, °C
t – is a current temperature, °C
label – is a label of a temperature sensor, it is specified in the field «Memo» on the page «TEMPERATURE» of a device web interface. A label in the text of a notification is quoted. If a label is not specified (empty), then it is not included into SMS.
A notification about a temperature leaving the thresholds of a specified range:
TEMP.SENSOR n "label" OUT OF RANGE (t1 TO t2), NOW tC |
where:
n – is a number of a temperature sensor, 1..8
t1, t2 – is thresholds of a normal temperature range, °C
t – is a current temperature, °C
label – is a label of a temperature sensor, it is specified in the field «Memo» on the page «TEMPERATURE» of a device web interface. A label in the text of a notification is quoted. If a label is not specified (empty), then it is not included into SMS
A notification about of a humidity sensor failure (a sensor stopped responding when polling):
RHn "label" FAILED |
where:
n – is a number of a humidity sensor, 1..4
label – is a label of a humidity sensor, it is set in the field «Memo» on the page «HUMIDITY» of a device web interface. A label in the text of a notification is quoted. If a label is not specified (empty), then it is not included into SMS
A notification about the restoration of a humidity sensor operation (a sensor started responding while polling):
RHn "label" is OK, h% h_status, tC t_status |
where:
n – is a number of a humidity sensor, 1..4
h – is a relative humidity, %
t – is a current temperature, °C
h_status – is a humidity status, its possible values are: «below normal», «normal», «above normal»
t_status – is a temperature status, its possible values are: «below normal», «normal», «above normal»
label – is a label of a humidity sensor, it is specified in the field «Memo» on the page «HUMIDITY» of a device web interface. A label in the test of a notification is quoted. If a label is not specified (empty), then it is not included into SMS
A notification about the values of relative humidity dropping below a specified range:
RHn "label" h% (below normal h1..h2%) |
where:
n – is a number of a humidity sensor, 1..4
h – is a relative humidity, %
h1, h2 – are the thresholds of a normal relative humidity range, %
label – is a label of a humidity sensor, which is specified in the field «Memo» on the page «HUMIDITY» of a device web interface. A label in the text of a notification is quoted. If a label is not specified (empty), then it is not included into SMS
A notification about the notifications of a relative humidity entering the normal specified range:
RHn "label" h% (normal h1..h2%) |
where:
n – is a number of a humidity sensor, 1..4
h – is a relative humidity, %
h1, h2 – are the thresholds of the normal relative humidity range, %
label – is a label of a humidity sensor, it is specified in the field «Memo» on the page «HUMIDITY» of a device web interface. A label is quoted in a text of a notification. If a label is not specified (empty), then it is not included into SMS
A notification about the readings of a relative humidity increasing the specified range:
RHn "label" h% (above normal h1..h2%) |
where:
n – is a number of a humidity sensor, 1..4
h – is a relative humidity, %
h1, h2 – are the thresholds of a normal relative humidity, %
label – is a label of a humidity sensor, it is set in the field «Memo» on the page «HUMIDITY» of a device web interface. A label is quoted in a text. If a label is not set (empty), then it is not included into SMS
A notification about temperature reading decreasing below a specified range (a temperature sensor is built into a relative humidity sensor):
RHn "label" tС (below normal t1..t2C) |
where:
n – is a number of a humidity sensor, 1..4
t – is a current temperature, °C
t1, t2 – are the thresholds of a normal temperature range, °C
label – is a label of a humidity sensor, it is specified in the field «Memo» on the page «HUMIDITY» of a device web interface. A label is quoted in a text of a notification. If a label is not set (empty), then it is not included into SMS
A notification about temperature readings entering the normal specified range (a temperature sensor is built into a relative humidity sensor):
RHn "label" tС (normal t1..t2C) |
where:
n – is a number of a humidity sensor, 1..4
t – is a current temperature, °C
t1, t2 – are the thresholds of normal temperature range, °C
label – is a label of a humidity sensor, which is set in the field «Memo» on the page «HUMIDITY» of a device web interface. A label is quoted in a text of a notification. If a label is not set (empty), then it is not included into SMS
A notification about temperature readings leaving a specified range (a temperature sensor is built into a relative humidity sensor):
RHn "label" tС (above normal t1..t2C) |
where:
n – is a number of a humidity sensor, 1..4
t – is a current temperature, °C
t1, t2 – are the thresholds of a normal temperature range, °C
label – is a label of a humidity sensor, which is set in the field «Memo» on the page «HUMIDITY» of a device web interface. A label is quoted in a text of a notification. If a label is not set (empty), then it is not included into SMS
A notification about an analog smoke sensor switching to a normal status:
ANALOG SMOKE SENSOR: OK |
A notification about analog smoke sensor switching to a status switched off (power is switched off):
ANALOG SMOKE SENSOR: NOT POWERED |
A notification about an analog smoke sensor switching to the status «Alarm»:
ANALOG SMOKE SENSOR: ALARM! |
A notification about an analog smoke sensor switching to the status «Open loop»:
ANALOG SMOKE SENSOR: FAILED (OPEN LOOP) |
A notification about an analog smoke sensor switching to the status «Short circuit»:
ANALOG SMOKE SENSOR: FAILED (SHORT CIRCUIT) |
A notification about switching on/off a built-in relay:
RELAY n "label" SWITCHED ON|OFF |
where:
n – is a relay number
label – is a relay label, which is set in the field «Memo» on the page «RELAY MANAGEMENT» of a device web interface. A label is quoted ina text of a notification. If a label is not set (empty), then it is not included into SMS
A notification about triggering the module «Watchdog» (a relay is switched on/off for short time to restore the operation of a device connected to it):
WDOG n "label" RESET |
where:
n – is a number of the channel of the module «Watchdog»
label – is a relay label, which is set in the field «Memo» on the page «RELAY MANAGEMENT» of a device web interface. A label is quoted in a text of a notification. If a label is not set (empty), then it is not included into SMS
A notification about restoring/losing a connection of a tested node in a network (the module «Pinger»):
PINGER STATUS: OK|FAILED (IP/HOSTNAME) |
where:
IP/HOSTNAME – is an IP address/DNS name of a node tested in a network
A feature of sending a daily report as SMS notification about a status of sensors, IO lines, and relays is implemented in a device. More detailed information about configuring the time of sending this report can be read in the section «[ENG] 11.9. [DKSF 70/71.6 IU] Configuring Time of Sending a Daily Report about a Status of Sensors, IO Lines and Relays as SMS Notifications».