[DKSF 54.1 IU] Page TEMPERATURE web interface

On this page readings of temperature sensors that are connected to a device are displayed.

Certain devices support connecting temperature sensors of TS WT and 1-wire types simultaneously (it can be clarified in the document named User Guide for a device). For TS and WT sensors, number of sensors 1..8 on a web-page of an interface correspond to the numbers labeled on cases of the sensors. Readings of TS and WT sensors will automatically appear in a web-interface 15s after a connection.

A 1-Wire sensor is not recommended to be linked to a sensor Х, if TS or WT sensor with the number X is already connected to a device. 1-Wire sensors have a higher priority than TS and WT sensors. If a conflict arises, a device will display readings of 1-Wire sensor.

To connect a 1-Wire sensor, there is a need to link its unique number to a sensor X in a filed “1W Sensor Unique Number”.

Unique number of a 1-Wire sensor can be known using any Netping device supporting 1-Wire. To fulfill this:

  1. Unplug all 1-Wire sensors from a device
  2. Plug a sensor, which number you want to know, to a device; 
  3. Go to http://<ip_device_address>/ow_new.cgi . On default, http://192.168.0.100/ow_new.cgi .A unique number of the sensor will be displayed in a browser window. A unique number of a 1-Wire sensor looks like the following: 288d f50a 0500 00e4 (16 hexadecimal numbers 0..9,a..f; starting from 28).

It is possible to plug up to 8 temperature sensors to a device.

Temperature values and temperature sensors statuses are updated automatically more than once a minute with no need to reload a page manually.

Note – is a filed for setting up a brief description of a temperature sensor. A note is used in Syslog and Logfile notifications as well as included into Trap notifications. Its maximum size is 16 characters. On default: empty

Current temperature, °C – displays a current temperature of a sensor in degrees of Celsius. A temperature value is occasionally updated automatically without reloading a web-page.

Status – displays a current status of a temperature sensor. Possible values:

  • Failure – a temperature sensor is not connected nor does not respond;
  • Normal – a temperature sensor responds, and a temperature value is within a specified Safe range for this temperature sensor;
  • Above Safe range - a temperature sensor responds and a temperature value exceeds a specified Safe range for this temperature sensor;
  • Below Safe range - a temperature sensor responds and a temperature value falls below a specified Safe range for this temperature sensor

Upper limit of Safe range, °C - is a field for setting up an upper limit of a temperature range for each temperature sensor. A temperature range is used to indicate conditions of TRAP and Syslog notifications generating. On default: 60

Lower limit of Safe range, °C - is a field for setting up a lower limit of a temperature range for each temperature sensor. A temperature range is used to indicate conditions of TRAP and Syslog notifications generating. On default: 10


When clicking the button "Settings" there appears a menu of settings for sending notifications to the following directions: Logfile, Syslog, E-mail, SMS and SNMP Trap

t° is above safe range – is a checkbox, when checked a device will send notifications if a current temperature of a temperature sensor exceeds an upper limit of a safe range for this temperature sensor. On default: checkbox is not checked

t° is in safe rangeis a checkbox, when checked a device will send notifications if a current temperature of a temperature sensor is back to a safe range for this temperature sensor. On default: checkbox is not checked

t°is below safe rangeis a checkbox, when checked a device will send notifications if a current temperature of a temperature sensor falls below a safe range for this temperature sensor. On default: checkbox is not checked

Sensor fault – is a checkbox, when checked a device will send notifications if a connection with a sensor is lost.  On default: 0

Include in Summary Report - is a checkbox, when checked reports about a sensor status will be sent via an e-mail and/or an sms.

A time for sending reports is indicated on the page SMS and E-MAIL settings.


After setting all necessary changes click the button «Apply changes».