[ENG] 11.7. [DKSF 70/71.5 IU] What SMS Notifications Can a Device Send?

The information in the section corresponds to a device UniPing server solution v3/SMS with a built-in GSM modem.

A maximum length of SMS notifications cannot exceed 70 Latin or Cyrillic characters.

Syntax of SMS Notifications

SMS notifications look as follows:

np_name (q) information

where:

np_name – is a name of a device for identification SMS notifications. It is specified at the page «SETUP» of a device web interface. If a name of a device is not set, then the name NETPING is used

 is a sequential number of a message. The number is nonvolatile  it is not zeroed when a power supply is switched off. It is used to register missed (lost) messages

Information – is an informational part of SMS notifications

Informational Part of SMS Notifications

A notification about changing a status of an IO line:

IOn=0|1 "label" "transcript"

where:

n – is a number of an IO line, 1..4

label – is a label of an IO line, which is set in the field «Memo» at the page «INPUT-OUTPUT» of a device web interface. If a label is not specified (empty), then it is not included into SMS.

transcript – is a description of a logic level of an IO line, which is set in the pop-up dialog of setting notifications from IO lines at the page «INPUT-OUTPUT» of a device web interface. If a description is not set (empty), then it is not included into SMS.

 

A notification about a failure of a temperature sensor (a sensor stopped responding during requesting):

TEMP.SENSOR "label" IS FAILED

where:

j – is a number of a temperature sensor, 1..8

label – is a label of a temperature sensor, it is set in the fields «Memo» at the page «TEMPERATURE SENSORS» of a device web interface. A label in a text of a notification is quoted. If a label is not set (empty), then it is not included into SMS

 

A notification about a normal status of a temperature within the thresholds of a specified range at the page «TEMPERATURE SENSORS» of a device web interface:

TEMP.SENSOR j "label" IN SAFE RANGE (t1 TO t2), NOW tC

where:

t – is a current temperature, °C

j – is a number of a temperature sensor, 1..8

t1, t2 – are thresholds of a «normal range», deg.С

label – is a label of a temperature sensor, which is set in the fields «Memo» at the page «TEMPERTURE SENSORS» of a device web interface. A label is quoted in the text of a notification. If a label is not specified (empty), then it is not included into SMS.

 

A notification about a temperature left the threshold of a specified range:

TEMP.SENSOR "label" OUT OF RANGE (t1 TO t2), NOW tC

where:

t – is a current temperature, °C

t1, t2 – are thresholds of a «normal range» of a temperature, °C

j – is a number of a temperature range, 1..8

label – is a label of a temperature sensor, which is set in the fields «Memo» at the page «TEMPERATURE SENSORS» of a device web interface. A label is quoted in the text of a notification. If a label is not specified (empty), then it is not included into SMS

 

A notification about a failure of a humidity sensor (a sensor stopped responding when requesting):

RHn "label" FAILED

where:

n – is a humidity sensor number, 1..4

label – is a label of a humidity sensor, which is set in the fields «Memo» at the page «HUMIDITY SENSORS» of a device web interface. A label is quoted in the text of a notification. If a label is not specified (empty), then it is not included into SMS

 

A notification about restoring an operability of a humidity sensor (a sensor started to respond when requesting):

RHn "label" is OK, h% is normal, tC is normal

where:

n – is a humidity sensor number, 1..4

– is a relative humidity, %

t – is a current temperature, °C

label – is a humidity sensor label, which is set in the fields «Memo» at the page «HUMIDITY SENSORS» of a device web interface. A label is quoted in a text of a notification. If a label is not specified (empty), then it is not included into SMS

 

A notification about readings of a humidity sensor decreased a specified range:

RHn "label" h% (below normal h1..h2%)

where:

– is a number of a humidity sensor, 1..4

– is a relative humidity, %

h1, h2 – are the thresholds of a «normal range» of a relative humidity, %

label – is a humidity sensor label, which is set in the fields «Memo» at the page «HUMIDITY SENSORS» of a device web interface. A label is quoted in a text of a notification. If a label is not specified (empty), then it is not included into SMS

 

A notification about readings of a relative humidity returned to the specified safe range:

RHn "label" h% (normal h1..h2%)

where:

– is a number of a humidity sensor, 1..4

– is a relative humidity, %

h1, h2 – are thresholds of a «normal range» of a relative humidity, %

label – is a humidity sensor label, which is set in the fields «Memo» at the page «HUMIDITY SENSORS» of a device web interface. A label is quoted in a text of a notification. If a label is not specified (empty), then it is not included into SMS

 

A notification about readings of a relative humidity increased a specified range:

RHn "label" h% (above normal h1..h2%)

where:

– is a number of a humidity sensor, 1..4

– is a relative humidity, %

h1, h2 – are thresholds of a «normal range» of a relative humidity, %

label – is a humidity sensor label, which is set in the fields «Memo» at the page «HUMIDITY SENSORS» of a device web interface. A label is quoted in a text of a notification. If a label is not specified (empty), then it is not included into SMS

 

A notification about temperature readings falling below a specified range (a temperature sensor is built inro a relative humidity sensor):

RHn "label" (below normal t1..t2C)

where:

– is a number of a humidity sensor, 1..4

t  - is a current temperature, °C

t1, t2 – are thresholds of a «normal» range of a temperature, °C

label – is a humidity sensor label, which is set in the fields «Memo» at the page «HUMIDITY SENSORS» of a device web interface. A label is quoted in a text of a notification. If a label is not specified (empty), then it is not included into SMS

 

A notification about temperature readings coming back to normal specified range (a temperature sensor is built into a relative humidity sensor):

RHn "label" (normal t1..t2C)

where:

– is a humidity sensor number, 1..4

t – is a current temperature, °C

t1, t2 – are thresholds of «normal» safe range of a temperature, °C

label – is a humidity sensor label, which is set in the fields «Memo» at the page «HUMIDITY SENSORS» of a device web interface. A label is quoted in a text of a notification. If a label is not specified (empty), then it is not included into SMS

 

A notification about temperature readings exceeding a specified range (a temperature sensor is built into a relative humidity sensor):

RHn "label" (above normal t1..t2C)

where:

– is a humidity sensor number, 1..4

t – is a current temperature, °C

t1, t2 – are thresholds of a «normal» range of a temperature, °C

label – is a humidity sensor label, which is set in the fields «Memo» at the page «HUMIDITY SENSORS» of a device web interface. A label is quoted in a text of a notification. If a label is not specified (empty), then it is not included into SMS

 

A notification about switching an analogue smoke sensor to a normal status:

ANALOG SMOKE SENSOR: OK

 

A notification about switching an analogue smoke sensor into a switched off status (power is disabled):

ANALOG SMOKE SENSOR: NOT POWERED

 

A notification about switching an analogue smoke sensor into a status «Alarm»:

ANALOG SMOKE SENSOR: ALARM!

 

A notification about switching an analogue smoke sensor to a status «Open Loop»:

ANALOG SMOKE SENSOR: FAILED (OPEN LOOP)

 

A notification about switching an analogue smoke sensor into a status «Short Circuit»:

ANALOG SMOKE SENSOR: FAILED (SHORT CIRCUIT)

 

A notification about switching on/off a built-in relay:

RELAY "label" SWITCHED ON|OFF

where:

n – is a relay number

label – is a relay label, which is set in the field «Memo» at the page «Relay Management» of a device web interface. A label is quoted in the text of a message. If a label is not specified (empty), then it is not included into SMS

 

A notification about triggering the module «Watchdog» (a socket is switched off for a short time to restore the operation of a connected device):

WDOG n "label" RESET

where:

n – is a relay number

label – is a relay label, which is set in the field «Memo» at the page «RELAY MANAGEMENT» of a device web interface. A label is quoted in the text of a message. If a label is not set (empty), then it is not included into SMS

 

A notification about restoring and losing a connection with a specified address  («PINGER» module):

PINGER STATUS: OK|FAILED (IP/HOST)

where:

IP/HOST – is an address of a checked IP address/host

Periodic SMS Reports about a Status of Sensors, IO Lines and Relays

A feature of sending a daily report as SMS notification about a status of sensors, IO lines and relays is implemented in a device. You can read more detailed information about configuring this report in the section «11.9. [DKSF 70/71.5 IU] Configuring Time of Sending a Daily Report about a Status of Sensors, IO Lines and Relays in SMS Notifications».