[ENG] 12.3. [DKSF 54.3 IU] How to Configure Pinger in the Module «Logic»?

To configure pinger, there is a need to go to the page «LOGIC» of a device web interface:

Link to the Logic page of a NetPing 4PWR-220 v4SMS device

In the section «Pinger», it is possible to configure testing the availability of the specified address via a network. A result of a test (pinger status) can be chosen as an «input» for a logic rule. It is possible to learn how to configure a rule in the module «Logic», from reading the section «[ENG] [Draft]12.2. [DKSF 54.3 IU] How to Use the Module «Logic»?». It is possible to configure up to two pingers – «PINGER 1», «PINGER 2». Typical using of pinger is automatic powering on the backup equipment when a connection line fails.

Configuring a pinger in a NetPing 4PWR-220 v4SMS device

where:

Address – IP is used as a destination address for polling (for example, 10.10.0.1) or FQDN (for example, test.example.net). An empty line disables polling. On default: empty line

Polling Period, s (5-900) – a value is chosen taking into account how rapidly the fault must be discovered. Also, there is a need to take into account that too frequent switching of a power supply can decrease a lifetime of the equipment. If there is no response ,ICMP echo (ping) is repeated after a timeout is over, and not when the next polling period starts. On default: 15

Ping Timeout, 100-10000ms waiting time for a «ping» response. Timeout is chosen after considering the operation speed of a local network taking into account the frequency of repeating unresponded «pings». If there is no response to «ping» when the specified timeout is over, sending «ping» is repeated immediately. If there is no response after 5 repeated sendings, a pinger status is changed to «silent», and repeats are stopped until the next polling period. On default: 1000

Status its possible values are: «responds», «silent», «-». If polling is not completed, a status can be undefined. In this case, the rules that depend on a pinger status do not form any commands, and their outputs are controlled by other rules or keep previous statuses. A pinger status is updated automatically nearly 4 times a minute. Request (sending ping) and a status update are executed with a period specified in the settings. If there is no response, polling is repeated 4 times (impossible to change) with timeout specified in the settings (the maximum time of waiting for a response).

If domain names are used, there is a need to take into account that the module «Logic» will not be able to determine the availability of the requested address because of the unavailability of a DNS server or no IP address in the settings of the DNS. «Pinger» is switched to the «silent» status.

After setting pinger values, there is a need to click the button «Apply changes».