[ENG] [IOv2] Resetting Parameters to Default Values
To reset parameters to default values, perform the next actions:
- Power off a device;
- Install a jumper;
- Switch power on;
- Remove a jumper 5-10 seconds after switching power on.
If a procedure is performed successfully, a LED light will blink initiating reset of parameters.
On default, the next parameters of a device are set:
User name: visor
Password: ping
IP address: 192.168.0.100
Subnetwork mask: 255.255.255.0
Gateway: not set
SNMPcommunity: SWITCH
MAC-address: 00 a2 xx xx xx xx
Here xx xx xx xx corresponds to a serial number of a device. Thus, all devices after being manufactured have unique MAC-addresses.
After resetting parameters to default settings there is a need to do an initial configuration of a device.