[ENG] 11.7. [DKSF 70/71.6 IU] What SMS Notifications a Device Can Send?

Information in the section applies to the device UniPing server solution v3/SMS with a built-in GSM modem.

Syntax of SMS Notifications

SMS notifications look like the following:

np_name (q) information

where:

np_name – is a name of a device for identification of SMS notifications. It is specified on the page «SETUP» of a device web interface. If a name of a device is not specified, then the name «NETPING» is used

 is a consequent number of notifications. A number is non-volatile  it is not zeroed when the power is switched off. It is used for a registration of missed (lost) notifications

Information – is an informational part of SMS notifications

Informational Part of SMS Notifications

Notification about changing a status of an IO line:

IOn=0|1 label transcript

where:

n –  is a number of an IO line, 1..8

label – is a label of an IO line, is specified in the field «Memo» on the page «DISCRETE IO» of a device web interface. If a label is not set (empty), then it is not included into SMS.

transcript – is a description of a logic level of an IO line, it is set in the pop-up dialogue for configuring notifications from IO lines on the page «DISCRETE IO» of a device web interface. If a description is not set (empty), then it is not included into SMS.


A notification about a failure of a temperature sensor (a sensor stopped responding while polling):

TEMP.SENSOR n "label" IS FAILED

where:

n – is a number of a temperature sensor, 1..8

label – is a label of a temperature sensor, it is specified in the field «Memo» on the page «TEMPERATURE» of a device web interface. A label in the text of a notification is quoted. It a label is not set (empty), then it is not included into SMS


A notification about a normalization of temperature within the thresholds of a specified range on the page «TEMPERATURE» of a device web interface:

TEMP.SENSOR n "label" IN SAFE RANGE (t1 TO t2), NOW tC

where:

n – is a number of a temperature sensor, 1..8

t1, t2 – are the thresholds of the normal temperature range, °C

t – is a current temperature, °C

label – is a label of a temperature sensor, it is specified in the field «Memo» on the page «TEMPERATURE» of a device web interface. A label in the text of a notification is quoted. If a label is not specified (empty), then it is not included into SMS.


A notification about a temperature leaving the thresholds of a specified range:

TEMP.SENSOR n "label" OUT OF RANGE (t1 TO t2), NOW tC

where:

n – is a number of a temperature sensor, 1..8

t1, t2 – is thresholds of a normal temperature range, °C

t – is a current temperature, °C

label – is a label of a temperature sensor, it is specified in the field «Memo» on the page «TEMPERATURE» of a device web interface. A label in the text of a notification is quoted. If a label is not specified (empty), then it is not included into SMS


A notification about of a humidity sensor failure (a sensor stopped responding when polling):

RHn "label" FAILED

where:

n – is a number of a humidity sensor, 1..4

label – is a label of a humidity sensor, it is set in the field «Memo» on the page «HUMIDITY» of a device web interface. A label in the text of a notification is quoted. If a label is not specified (empty), then it is not included into SMS


A notification about the restoration of a humidity sensor operation (a sensor started responding while polling):

RHn "label" is OK, h% h_status, tC t_status

where:

n – is a number of a humidity sensor, 1..4

– is a relative humidity, %

t – is a current temperature, °C

h_status – is a humidity status, its possible values are: «below normal», «normal», «above normal»

t_status – is a temperature status, its possible values are: «below normal», «normal», «above normal»

label – is a label of a humidity sensor, it is specified in the field «Memo» on the page «HUMIDITY» of a device web interface. A label in the test of a notification is quoted. If a label is not specified (empty), then it is not included into SMS


A notification about the values of relative humidity dropping below a specified range:

RHn "label" h% (below normal h1..h2%)

where:

– is a number of a humidity sensor, 1..4

– is a relative humidity, %

h1, h2 – are the thresholds of a normal relative humidity range, %

label – is a label of a humidity sensor, which is specified in the field «Memo» on the page «HUMIDITY» of a device web interface. A label in the text of a notification is quoted. If a label is not specified (empty), then it is not included into SMS


A notification about the notifications of a relative humidity entering the normal specified range:

RHn "label" h% (normal h1..h2%)

where:

– is a number of a humidity sensor, 1..4

– is a relative humidity, %

h1, h2 – are the thresholds of the normal relative humidity range, %

label – is a label of a humidity sensor, it is specified in the field «Memo» on the page «HUMIDITY» of a device web interface. A label is quoted in a text of a notification. If a label is not specified (empty), then it is not included into SMS


A notification about the readings of a relative humidity increasing the specified range:

RHn "label" h% (above normal h1..h2%)

where:

– is a number of a humidity sensor, 1..4

– is a relative humidity, %

h1, h2 – are the thresholds of a normal relative humidity, %

label – is a label of a humidity sensor, it is set in the field «Memo» on the page «HUMIDITY» of a device web interface. A label is quoted in a text. If a label is not set (empty), then it is not included into SMS


A notification about temperature reading decreasing below a specified range (a temperature sensor is built into a relative humidity sensor):

RHn "label" (below normal t1..t2C)

where:

– is a number of a humidity sensor, 1..4

t – is a current temperature, °C

t1, t2 – are the thresholds of a normal temperature range, °C

label – is a label of a humidity sensor, it is specified in the field «Memo» on the page «HUMIDITY» of a device web interface. A label is quoted in a text of a notification. If a label is not set (empty), then it is not included into SMS

 

A notification about temperature readings entering the normal specified range (a temperature sensor is built into a relative humidity sensor):

RHn "label" (normal t1..t2C)

where:

– is a number of a humidity sensor, 1..4

t – is a current temperature, °C

t1, t2 – are the thresholds of normal temperature range, °C

label – is a label of a humidity sensor, which is set in the field «Memo» on the page «HUMIDITY» of a device web interface. A label is quoted in a text of a notification. If a label is not set (empty), then it is not included into SMS


A notification about temperature readings leaving a specified range (a temperature sensor is built into a relative humidity sensor):

RHn "label" (above normal t1..t2C)

where:

– is a number of a humidity sensor, 1..4

t – is a current temperature, °C

t1, t2 – are the thresholds of a normal temperature range, °C

label – is a label of a humidity sensor, which is set in the field «Memo» on the page «HUMIDITY» of a device web interface. A label is quoted in a text of a notification. If a label is not set (empty), then it is not included into SMS


A notification about an analog smoke sensor switching to a normal status:

ANALOG SMOKE SENSOR: OK


A notification about analog smoke sensor switching to a status switched off (power is switched off):

ANALOG SMOKE SENSOR: NOT POWERED


A notification about an analog smoke sensor switching to the status «Alarm»:

ANALOG SMOKE SENSOR: ALARM!


A notification about an analog smoke sensor switching to the status «Open loop»:

ANALOG SMOKE SENSOR: FAILED (OPEN LOOP)


A notification about an analog smoke sensor switching to the status «Short circuit»:

ANALOG SMOKE SENSOR: FAILED (SHORT CIRCUIT)


A notification about switching on/off a built-in relay:

RELAY n "label" SWITCHED ON|OFF

where:

n – is a relay number

label – is a relay label, which is set in the field «Memo» on the page «RELAY MANAGEMENT» of a device web interface. A label is quoted ina text of a notification. If a label is not set (empty), then it is not included into SMS


A notification about triggering the module «Watchdog» (a relay is switched on/off for short time to restore the operation of a device connected to it):

WDOG n "label" RESET

where:

n – is a number of the channel of the module «Watchdog»

label – is a relay label, which is set in the field «Memo» on the page «RELAY MANAGEMENT» of a device web interface. A label is quoted in a text of a notification. If a label is not set (empty), then it is not included into SMS


A notification about restoring/losing a connection of a tested node in a network (the module «Pinger»):

PINGER STATUS: OK|FAILED (IP/HOSTNAME)

where:

IP/HOSTNAME – is an IP address/DNS name of a node tested in a network

Periodic SMS Reports about a Status of Sensors, IO Lines and Relays

A feature of sending a daily report as SMS notification about a status of sensors, IO lines, and relays is implemented in a device. More detailed information about configuring the time of sending this report can be read in the section «[ENG] 11.9. [DKSF 70/71.6 IU] Configuring Time of Sending a Daily Report about a Status of Sensors, IO Lines and Relays as SMS Notifications».