[ENG] 5.4. [DKSF 54.2 IU] Browsing Readings and Configuring Parameters of Humidity Sensors in a Web Interface
To browse readings and configure parameters of humidity sensors, there is a need to go to the page «HUMIDITY» of a device web interface:
where:
Relative humidity – are readings of a sensor, which determine a relative humidity, in %.
Status of RH – is a parameter, which determines a status of a humidity sensor in a current moment of time. Possible variants are: «failure», «below normal», «normal», «above normal».
Temperature – are readings of a temperature sensor, which is embedded into a humidity sensor, in °C.
Status of temperature – a parameter determines a status of a temperature sensor, embedded into a humidity sensor in a current moment of time. Possible variants are: «failure», «below normal», «normal», «above normal».
Top margin of Humidity Safe Range, % – is a humidity value, when exceeded a sensor is switched to the status «above normal». A hysteresis is ± 1 percent point. On default: 85
Bottom margin of Humidity Safe Range, % – is a humidity value, when decreased, a sensor is switched to the status «below normal». A hysteresis is ± 1 percent point. On default: 5
Top margin of Temperature Safe Range, °C – is a temperature value, when exceeded a sensor is switched to the status «above normal». A hysteresis is ± 1°C. On default: 60
Bottom margin of Temperature Safe Range, °C – is a temperature value, which decreased a sensor is switched to the status «below normal». A hysteresis is ± 1°C. On default: 10
Dew Point – is a temperature of a dew point, which is calculated according to readings of a relative humidity and temperature, in °C.