[ENG] 5.4. [DKSF 54.3 IU] Viewing Readings and Configuring Parameters of Humidity Sensors in a Web Interface
To view readings and configure parameters of humidity sensors, there is a need to go to the page «HUMIDITY» of a device web interface:
where:
- Relative humidity – is readings of the sensor that determines a relative humidity, in %;
- Status of RH – a parameter determines a status of a humidity sensor in a current moment of time. Possible variants are: «Failed», «Below Safe», «Safe», «Above Safe»;
- Temperature – is readings of a temperature sensor that is built into a humidity sensor, °C
- Status of Temperature – a parameter determines a status of a temperature sensor that is built into a humidity sensor in a current moment of time. Possible variants are: «Failed», «Below Safe», «Safe», «Above Safe»;
- Top Margin of Humidity Safe Range, % – is a humidity value, when exceeded a sensor is switched to the status «Above safe». Hysteresis is ± 1 percentage point. On default: 85;
- Bottom Margin of Humidity Safe Range, % – is a humidity value, when decreased a sensor is switched to a status «Below safe». Hysteresis is ± 1 percentage point. On default: 5;
- Top Margin of Temperature Safe Range, °C – is a temperature value, when exceeded, a sensor is switched to a status «Above safe». Hysteresis is ± 1°C. On default: 60;
- Bottom Margin of Temperature Safe Range, °C – is a temperature value, when decreased, a sensor is switched to a status «Below safe». Hysteresis is ± 1°C. On default: 10;
- Dew Point – is a temperature of a dew point that is calculated using readings of a relative humidity and temperature, in °C.